Table of Contents
Benefits of Using Auxiliary Transformers in Power Systems
Auxiliary transformers play a crucial role in power systems by stepping Down voltage Levels to a more manageable range for distribution and utilization. These transformers are essential components that help ensure the efficient and reliable operation of electrical systems. In this article, we will explore the benefits of using auxiliary transformers in power systems and why they are a vital part of any electrical infrastructure.
model | Rating\\u00a0capacity\\u00a0\\uff08KVA\\uff09 | Off-load\\u00a0losses\\uff08W\\uff09 | Voltage\\u00a0combination\\u00a0\\uff08KV\\uff09 | Load\\u00a0losses\\uff08W\\uff09 | Off-load\\u00a0current\\u00a0\\uff08%\\uff09 | Short-circuit\\u00a0voltage\\u00a0\\uff08%\\uff09 |
S11-M-30 | 30 | 100 | 6,6.3,10,10.5,11/0.4 | 600 | 2.3 | 4.0 |
S11-M-50 | 50 | 130 | 6,6.3,10,10.5,11/0.4 | 870 | 2.0 | 4.0 |
S11-M-63 | 63 | 150 | 6,6.3,10,10.5,11/0.4 | 1040 | 1.9 | 4.0 |
S11-M-80 | 80 | 180 | 6,6.3,10,10.5,11/0.4 | 1250 | 1.9 | 4.0 |
S11-M-100 | 100 | 200 | 6,6.3,10,10.5,11/0.4 | 1500 | 1.8 | 4.0 |
S11-M-125 | 125 | 240 | 6,6.3,10,10.5,11/0.4 | 1800 | 1.7 | 4.0 |
S11-M-160 | 160 | 280 | 6,6.3,10,10.5,11/0.4 | 2200 | 1.6 | 4.0 |
S11-M-200 | 200 | 340 | 6,6.3,10,10.5,11/0.4 | 2600 | 1.5 | 4.0 |
S11-M-250 | 250 | 400 | 6,6.3,10,10.5,11/0.4 | 3050 | 1.4 | 4.0 |
S11-M-315 | 315 | 480 | 6,6.3,10,10.5,11/0.4 | 3650 | 1.4 | 4.0 |
S11-M-400 | 400 | 570 | 6,6.3,10,10.5,11/0.4 | 4300 | 1.3 | 4.0 |
S11-M-500 | 500 | 680 | 6,6.3,10,10.5,11/0.4 | 5100 | 1.2 | 4.0 |
S11-M-630 | 630 | 810 | 6,6.3,10,10.5,11/0.4 | 6200 | 1.1 | 4.5 |
S11-M-800 | 800 | 980 | 6,6.3,10,10.5,11/0.4 | 7500 | 1.0 | 4.5 |
S11-M-1000 | 1000 | 1150 | 6,6.3,10,10.5,11/0.4 | 10300 | 1.0 | 4.5 |
S11-M-1250 | 1250 | 1360 | 6,6.3,10,10.5,11/0.4 | 12800 | 0.9 | 4.5 |
S11-M-1600 | 1600 | 1640 | 6,6.3,10,10.5,11/0.4 | 14500 | 0.8 | 4.5 |
S11-M-2000 | 2000 | 2280 | 6,6.3,10,10.5,11/0.4 | 17820 | 0.6 | 5.0 |
S11-M-2500 | 2500 | 2700 | 6,6.3,10,10.5,11/0.4 | 20700 | 0.6 | 5.0 |
S11-M-30- | 30 | 90 | 20,22/0.4 | 660 | 2.1 | 5.5 |
S11-M-50- | 50 | 130 | 20,22/0.4 | 960 | 2 | 5.5 |
S11-M-63- | 63 | 150 | 20,22/0.4 | 1145 | 1.9 | 5.5 |
S11-M-80- | 80 | 180 | 20,22/0.4 | 1370 | 1.8 | 5.5 |
S11-M-100- | 100 | 200 | 20,22/0.4 | 1650 | 1.6 | 5.5 |
S11-M-125- | 125 | 240 | 20,22/0.4 | 1980 | 1.5 | 5.5 |
S11-M-160- | 160 | 290 | 20,22/0.4 | 2420 | 1.4 | 5.5 |
S11-M-200- | 200 | 330 | 20,22/0.4 | 2860 | 1.3 | 5.5 |
S11-M-250- | 250 | 400 | 20,22/0.4 | 3350 | 1.2 | 5.5 |
S11-M-315- | 315 | 480 | 20,22/0.4 | 4010 | 1.1 | 5.5 |
S11-M-400- | 400 | 570 | 20,22/0.4 | 4730 | 1 | 5.5 |
S11-M-500 | 500 | 680 | 20,22/0.4 | 5660 | 1 | 5.5 |
S11-M-630 | 630 | 810 | 20,22/0.4 | 6820 | 0.9 | 6 |
S11-M-800 | 800 | 980 | 20,22/0.4 | 8250 | 1.8 | 6 |
S11-M-1000 | 1000 | 1150 | 20,22/0.4 | 11330 | 0.7 | 6 |
S11-M-1250 | 1250 | 1350 | 20,22/0.4 | 13200 | 0.7 | 6 |
S11-M-1600 | 1600 | 1630 | 20,22/0.4 | 15950 | 0.6 | 6 |
One of the primary benefits of using auxiliary transformers is their ability to step down voltage levels from medium to low voltage, making it safer and more practical for distribution and use. By reducing the voltage to a more manageable level, auxiliary transformers help prevent electrical accidents and equipment damage that can occur when high voltage levels are present. This is especially important in industrial settings where high voltage equipment is used, as it helps protect both workers and machinery from potential hazards.
Another benefit of using auxiliary transformers is their ability to improve the efficiency of power distribution systems. By stepping down voltage levels, these transformers help reduce energy losses that occur during transmission and distribution. This not only helps save energy but also reduces operating costs for power companies and end-users. Additionally, auxiliary transformers help improve the overall reliability of power systems by providing a stable and consistent source of power to electrical equipment.
In addition to their functional benefits, auxiliary transformers also offer practical advantages for power system operators. These transformers are typically compact and easy to install, making them ideal for use in a variety of applications. They are also designed to be durable and reliable, ensuring long-term performance and minimal maintenance requirements. This makes them a cost-effective solution for power system operators looking to improve the efficiency and reliability of their electrical infrastructure.
When it comes to sourcing auxiliary transformers, China has emerged as a leading exporter and maker of high-quality transformers. Chinese manufacturers are known for their expertise in transformer technology and their ability to produce transformers that meet international standards for performance and Safety. Many Chinese transformer manufacturers offer quick shipment options, allowing customers to receive their orders in a timely manner. Additionally, some manufacturers provide instructional videos on how to install and maintain their transformers, making it easier for customers to use these products effectively.
In conclusion, auxiliary transformers play a critical role in power systems by stepping down voltage levels and improving the efficiency and reliability of electrical infrastructure. These transformers offer a range of benefits, including increased safety, energy savings, and ease of installation. Chinese manufacturers are a reliable source of high-quality auxiliary transformers, offering quick shipment options and instructional videos to help customers make the most of their products. By incorporating auxiliary transformers into their power systems, operators can ensure a stable and efficient source of power for their electrical equipment.